POWER FACTOR CORRECTED DC POWER SUPPLY - PF Series

Features
High Power – upto 30KW with 24 to 110V DC and 20 to 1200A Range
19" Rack Construction
Power Factor Corrected (0.99 at full load) Input
Wide Input Range
Equal Current Sharing Parallel Operation for upto 12 Nos.
Abnormal Condition Alarm
Output Boost Facility
7 Segment Display for Voltage and Current Measurement
n + 1 redundancy
Upgradable
Power Factor Corrected DC Power Supply - PF Series
 
The PF Series Switching DC Power Supply, is Power Factor corrected, designed to deliver variable DC power upto 30KW in a constant voltage mode. It covers a current range from 20A to 1200A, in Four Voltage Settings (30KW max). Higher rated power supplies can also be supplied against specific requirements.
This range comes, housed in 19" rack mounting construction, with modules in multiples of 2.5KW each which can be connected in n+1 configuration with equal current sharing parallel operation of upto 12 modules. The DC Output power can be upgraded by adding modules on to the rack at a later stage. This provides maximum flexibility to the user to plan for future & order modules at a later stage.
The PF series power supply is used to simultaneously supply the DC load and recharge the battery. This type of DC system is widely used in Power Generation and Distribution, Instrumentation, Onshore and Offshore Petro-chemical applications etc.
 
Technical Specifications
INPUT
Voltage 176 - 265 V AC, 1ph, 2w (2 .5KW - 7.5kw)
305 - 465 3ph, 4w (above 7.5KW).
Frequency 45 - 65 Hz.
Power Factor 0.99 (at full load).
Spikes VDE 0843/IEC801-V-3-3.
Burst VDE 0843/IEC0801-IV-3-2.
RFI VDE 0878/EN55022-”A”.
OUTPUT 
Voltage 24V / 48V / 60V / 110V.
Line / Load Regulation Better than ±2%.
Ripple <200mV p-p.
Current 20 Amps to 1200 Amps (any one rating).
Power 2.5KW to 30KW max.
Recovery Time 1ms typical.
Parallel Operation One or more units can be used in parallel for higher power capacity.
METERING 7 Segment Display for Voltage and Current Measurement.
PROTECTIONS Over Voltage & Over Temp : Electronic turn off for Output Over-voltage and Over-temperature, Reset through panel push switch DC Overload.
INDICATIONS LED Green = Float. LED Red = Boost. LED Red = Output Abnormal.
7 Segment DPM for Output Voltage & Current measurement.
COLOR DA Grey.
GENERAL DATA
Operating Temp. 0ºC to +60ºC.
Derating 2.5% / ºC above +40ºC.
Storage Temp. -20ºC to +70ºC.
Humidity 90% without condensation.
Cooling Fan cooled with air exhaust at the rear.
Mech. Construction 19" x 4 unit high x 500 mm deep.
Encl. Protection IP-20.
Connector Terminal strip for input. Brass terminals for output at the rear.
Weight Approx. 18 Kg. per module.
 
O/P Voltage VDC
Current Amps
Nominal
Range
24
23-28
100
200
300
600
900
1200
48
46-56
50
100
150
300
450
600
60
58-70
40
80
120
240
360
480
110
100-130
20
40
60
120
180
240
 
 