Tel. : 91-022-25821861
Fax : 91-022-25823137
Email : response@aplab.com
|
|
 |
| KILOWATT DC REGULATED SUPPLIES - VO Series |
|
| Features |
 |
Highest Power
Maximum Power of 150KW upto 2000A and 450VDC. |
 |
Man Machine Interface
User Friendly Controls and Instant Access to Status. |
 |
6/12 Pulse Technology
Fully Controlled Rectifier. |
 |
Wide Input Range
Suitable for Indian Power Scene. |
 |
Unique Protection
Re-entrant / Shut-off Type for Overload/Short Circuit. |
 |
Flexible Design
26 Models to Choose. |
 |
Application Oriented
For Use in Aviation, Automobile, Process and Engineering Industry. |
|
|
| |
The VO Series are variable voltage DC power supplies, wherein the DC Voltage can be set from 10% to 100% of the rated capacity, over the specified line variation, and the load variation from no load to full load. This series has been specially designed to test DC input variation performance of the connected equipment. In addition it offers user selectable option of either Re-entrant/Shut-off type overload and short circuit protection. |
Re-entrant Type : During overload condition the output current is limited and when this condition is removed the voltage will build to set voltage automatically in soft-start mode. This is useful for applications where loads draw very high inrush current for a short period. |
Shut-off Type : During overload condition or short circuit the output will shut-off. The unit can be manually reset by ON/OFF switch. |
|
| |
| Technical Specifications |
| INPUT |
| Voltage |
415V AC ±10% (upto ±30% on request), 50Hz ±6%, 3Ø, 4 wire
or 3Ø, 3 wire.
Optional 230V AC ±10%, 1Ø, 2 wire-upto power level of 5KW. |
| OUTPUT |
| Voltage |
4 to 16, 32, 75 and 150V DC (any one voltage range). |
| Settability |
10%-100% (Optional - Remote voltage control facility can be provided). |
Line / Load Regulation |
±1% of rated O/P Voltage. |
| Ripple |
1% rms of rated O/P Voltage. |
| Current |
50A to 2000A Max. (any one rating). |
| Power |
150KW Max. (continous). |
Cabinet Encl. Protection |
IP-20, Optional (IP-21, IP-30, IP-31 or IP-40). |
| Cooling |
Forced Air Cooling. |
| Cabinet Color |
D.A. Grey. |
| Metering |
Analogue Meters for Output Voltage / Output Current.
Optional Input Voltage / Input Current.
Optional Digital Meters. |
| Protections |
Input Over/Under
Voltage, Phase Fail/Reversal (for 3 phase input), Output DC Overload/Shortcircuit,
Output DC Over voltage, Overheat, Soft-Start Feature, High Speed Fuses for Semi-Conductor Devices and Snubber Circuits for
power Semi-Conductor Devices. |
| Indications |
Mains ON, DC ON, Phase Fail (for 3 phase input), Mains Over/Under Voltage, DC Over/Under Voltage, DC Overload and Overheat. |
|
| |
| Selection Guide |
V / I |
50A |
100A |
300A |
500A |
1000A |
1500A |
2000A |
4-16 |
4/16-50 |
4/16-100 |
4/16-300 |
4/16-500 |
4/16-1000 |
4/16-1500 |
4/16-2000 |
10-32 |
10/32-50 |
10/32-100 |
10/32-300 |
10/32-500 |
10/32-1000 |
10/32-1500 |
10/32-2000 |
25-75 |
25/75-50 |
25/75-100 |
25/75-300 |
25/75-500 |
25/75-1000 |
25/75-1500 |
25/75-2000 |
50-150 |
50/150-50 |
50/150-100 |
50/150-300 |
50/150-500 |
50/150-1000 |
-- |
-- |
| Other
ratings on request upto 450V DC, 2000A with max. power of 150KW. |
|
| |
|