| KILOWATT DC REGULATED SUPPLIES - FO Series |
|
| Features |
 |
Highest Power
Maximum Power of 150KW upto 2000A and 450VDC. |
 |
Man Machine Interface
User Friendly Controls and Instant Access to Status. |
 |
6/12 Pulse Technology
Fully Controlled Rectifier. |
 |
Wide Input Range
Suitable for Indian Power Scene. |
 |
Unique Protection
Re-entrant / Shut-off Type for Overload/Short Circuit |
 |
Flexible Design
26 Models to Choose. |
 |
Application Oriented
For Use in Aviation, Automobile, Process and Engineering Industry. |
|
|
| |
The Aplab Fixed Output DC power Supplies- FO Series are state of the art technology, specifically designed to provide cost effective solutions for optimum performance. The output is preset type with provision for fine adjustment upto ±5% through front panel control and is available in various output configurations for compatibility. In addition it offers user selectable option of either Re-entrant/Shut-off type overload and short circuit protection. |
Re-entrant Type : During overload condition the output current is limited and when this condition is removed the voltage will build to set voltage automatically in soft- start mode. This is useful for applications where loads draw very high inrush current for a short period. |
Shut-off Type : During overload condition or short circuit the output will shut-off. The unit can be manually reset by ON/OFF switch. |
|
| |
| Technical Specifications |
| INPUT |
| Voltage |
415V AC ±10% (upto ± 30% on request), 50Hz ±6%, 3Ø, 4 wire or 3Ø, 3 wire.
Optional 230V AC ±10%, 1Ø, 2 wire -upto power level of 5KW. |
| OUTPUT |
| Voltage |
16, 32, 75 and 150V DC (any one voltage). |
| Settability |
± 5% (Optional - Remote voltage control facility can be provided). |
Line / Load
Regulation |
± 1% of rated O/P Voltage. |
| Ripple |
1% rms of rated O/P Voltage. |
| Current |
50A to 2000A Max. (any one rating). |
| Power |
150KW Max. (continous). |
Cabinet Encl. Protection |
IP-20, Optional (IP-21, IP-30, IP-31 or IP-40). |
| Cooling |
Forced Air Cooling. |
| Cabinet Color |
D.A. Grey. |
| Metering |
Analogue Meters for Output Voltage / Output Current.
Optional Input Voltage/Input Current.
Optional Digital Meters. |
| Protections |
Input
Over / Under Voltage, Phase Fail/Reversal (for 3 phase input), Output
DC Overload / Shortcircuit, Output DC Over voltage, Overheat, Soft-Start
Feature, High Speed Fuses for Semi-Conductor Devices and Snubber
Circuits for power Semi-Conductor Devices. |
| Indications |
Mains ON, DC ON, Phase Fail (for 3 phase input), Mains Over/Under Voltage,
DC Over/ Under Voltage, DC Overload and Overheat. |
|
| |
| Selection Guide |
V / I |
50A |
100A |
300A |
500A |
1000A |
1500A |
2000A |
16 |
16-50 |
16-100 |
16-300 |
16-500 |
16-1000 |
16-1500 |
16-2000 |
32 |
32-50 |
32-100 |
32-300 |
32-500 |
32-1000 |
32-1500 |
32-2000 |
75 |
75-50 |
75-100 |
75-300 |
75-500 |
75-1000 |
75-1500 |
75-2000 |
150 |
150-50 |
150-100 |
150-300 |
150-500 |
150-1000 |
-- |
-- |
| Other ratings on request upto 450V DC, 2000A with max. power of 150KW. |
|
| |
|