Tel. : 91-022-25821861
Fax : 91-022-25823137
Email : response@aplab.com
|
|
 |
| 1 TO 10KVA INVERTER SYSTEMS - IN Series |
|
| Features |
 |
State of the art Digital Technology Using IGBT/MOSFET Based Technique |
 |
True Sinewave System Distortion Free and Precise Sinewave Output |
 |
Highest Reliability For Your Precious and Critical Equipment |
 |
Compact Footprint Rugged Construction and Quiet Operation, Ideal for Telecom and Computer Environment |
 |
Man-Machine Interface User Friendly Display and Controls |
 |
Total Rated Power At Ambient as High as 45°C |
 |
Better Efficiency Means Lower Running Cost |
|
|
| |
The INVERTER-Series is designed for Telecom and Industrial, Heavy duty application, which delivers continous true sinewave output power with high stability and precise voltage, suitable for all types of Telecom, non-linear and linear loads. |
The INVERTER-Series covers the complete battery voltage range i.e. end voltage to boost voltage. The compact construction and silent operation makes it an ideal choice for use in human environment. The INVERTER-Series has range from 1KVA to 10KVA, higher capacity system can be configured on request. |
| |
Applications
Telecommunications, Railways, Utilities, Remote Area Systems and Engineering Industry. |
|
|
| Technical Specifications |
| MODEL |
|
IN1010 |
IN1030 |
IN1050 |
IN1100 |
| RATED POWER |
|
1.0KVA |
3.0KVA |
5.0KVA |
10.0KVA |
| INPUT |
Voltage (Nominal) |
48VDC. |
| Voltage (Range) |
-12.5% and +20%. |
| OUTPUT |
Voltage |
230V AC, SinglePhase (Optional -400VAC/415VAC, Three Phase). |
| Frequency |
50Hz ±0.5%. |
| Regulation |
±1% (Typical). |
| Transient Response |
±7 - 8% for 100% Load Variation. |
| Inverter Technology |
PWM (MOSFET) |
PWM (IGBT) |
| Waveform |
Pure Sinewave, THD <3% (Linear Load). |
Short Term Overload |
110% for 30 min, 150% for 10 secs and 200% for 5 cycles. |
| Efficiency (Peak) |
82 |
78 |
79 |
78 |
| Changeover (Optional) |
Transfer time (In sync mode) less than 5msec. |
Load Power Factor |
0.8 |
| GENERAL |
Protections |
DC Over/Under Voltage, Inverter Over/Under Voltage, Inverter Overload and Overheat. |
| LED Indications |
DC On, Inverter On, DC Over/Under Voltage, Inverter Overload, Overheat, Inverter Over/Under Voltage (Optional-Load on Inverter and Load On Aux. Supply). |
| Metering |
Analogue
(Optional 16 x 2 LCD for I/P & O/P Volts, Load% & Frequency). |
| Audible Alarm |
Built-in Buzzer Operates on Fault Conditions. |
| Cooling |
Forced Cooling. |
| Protection Class |
IP-21. |
| Finish |
DA Grey IS632. |
Weight (Kgs.)
(approx.) |
41 |
88 |
115 |
210 |
Dimensions
W x D x H (mm) |
500 x 450 x 400 |
400 x 650 x 750 |
400 x 650 x 750 |
600 x 550 x 1000 |
| # Other Input Voltages & Higher Capacity Rating Systems on Request. |
|
| |
|