UPS Systems 80KVA TO 150KVA - HP Series
3 Phase in / 1 Phase out

Features
80 - 150KVA in 4 Ratings
Sophisticated High Specification On Line Configuration with Optional Static Switch
State of the Art IGBT Based Pulse Width Modulation (PWM) Technology to Reduce Harmonic Distortion and Increase Both Crest Factor Tolerance and Dynamic Stability
Higher Efficiency of Operation Means Aplab UPS has Significantly Lower Running Costs than Leading Competitors
Continuously Delivers Full Rated Power at Ambient as high as 45ºC
Parallel Operation of UPS
Comprehensive Indication of Normal and Fault Conditions
Simple Operating Controls
Compatible with Sealed Maintenance Free Battery as well as Tubular Lead Acid Batteries
Compact Cabinet & Ultra Light Weight
Easy Installation with Wheels for Manoeuvreability and Front Terminal Box
Optional Remote Status Panel
Aplab 80KVA to 150KVA UPS
 
Technical Specifications
MODEL
HP1080
HP1100
HP1120
HP1150
RATED POWER (at PF 0.8)
80KVA
100KVA
120KVA
150KVA
INPUT 
Voltage Nominal
               Range
400V AC
340V AC to 460V AC.
Frequency Nominal
                    Range
50Hz.
47 to 53Hz.
Phase
Three Phase, 4 Wire.
AC to AC Efficiency
>88% peak
>89% peak
OUTPUT 
Power Max.
80KVA/64KW
100KVA/80KW
1200KVA/96KW
150KVA/120KW
Current
348 Amps.
435 Amps.
522 Amps.
652 Amps.
Voltage
230V AC.
Voltage Regulation
±1% Typical.
Frequency
50Hz.
Frequency Stability
±0.05%.
Phase
Single Phase.
Waveform
Sinewave.
Total Harmonic Distortion
Less than 2% with Linear Load.
TRANSIENT RESPONSE
(100% Load Step)
Less than ±5%.
RESPONSE TIME
Less than 60 milli-seconds to reach within ±2%.
LOAD POWER FACTOR RANGE
Unity to 0.8 Lag within specified max. output power ratings.
OVERLOAD RATING a) 1/2 Hour
b) 10 Seconds
c) 10 Cycles
120%
150%
200%   
PROTECTIONS a) Input Over/Under Voltage
b) Phase Fail
c) Overload at the Output
d) SOAR Protection for IGBTs
e) Output AC Over / Under voltage
g) High Speed Fuses for Semi-Conductor Devices
h) Snubber Circuits for Power Semi-Conductor Devices
INDICATIONS a) Mains On
b) Inverter On
c) Battery on Charge
d) Mains Over/Under Voltage
e) Phase Fail
f) Low Battery Imminent
g) Battery Over / Under Voltage
h) Inverter Over / Under Voltage
i) Inverter Overload
j) Overheat
AUDIBLE ALARM For Conditions from (d) to (j) a Local Buzzer operates.
REMOTE INDICATIONS A potential free contact is provided for fault indications and alarm.
COMPUTER INTERFACE RS-232 (Optional).
METERING 16 x 2 LCD to measure the following :
a) AC Input / Output Voltage per Phase
b) Load percentage
c) DC Voltage
d) Battery percentage
e) Output Frequency
BATTERY    
Nominal Voltage 384V DC.
Type Sealed maintenance free / tubular lead Acid Battery.
Standby Period
(Full Load at 0.8 PF)
30 Minutes (can be increased upto 2 hrs and extended further on request).
GENERAL    
Operating Temperature 0 to 45ºC.
Storage -20ºC to +65ºC.
Finish Cool Grey Shade No. 5-C & 1-C/DA Grey IS632.
Relative Humidity
Non Condensing
0 to 95%.
Enclosure Protection IP20.
Dimensions  HEIGHT
                         WIDTH
                         DEPTH
1800 mm
1000 mm
800 mm
1900 mm
1000 mm
800 mm
2000 mm
1100 mm
800 mm
2200 mm
1200 mm
900 mm
Weight
800 Kgs.
950 Kgs.
1050 Kgs.
1250 Kgs.
OPTIONAL STATIC SWITCH    
Transfer Time a) Less than 5 milli-seconds from inverter to mains.
b) Less than 5 milli-seconds from mains to inverter.
Indications a) Aux. Supply On
b) Load on Inverter
c) Load on Aux. Supply
d) Manual Bypass On
 
 