| Technical Specifications |
SINGLE PHASE MODELS |
| Model No. * |
9811 |
9812 |
9813 |
9814 |
Power Rating
(Max. continuous) |
400VA |
1KVA |
1.5KVA |
2KVA |
| Input Voltage (Primary) |
188V to 264V AC, 98V to 132V AC (For Suffix A) |
Output Voltage
(Secondary) |
188V to 264V AC, 98V to 132V AC (For Suffix A) |
Common Mode
Noise Rejection |
More than 130dB. |
| D.C. Galvanic Isolation |
More than 1000M ohms measured at 2.5KV between any windings or windings to case. |
| Breakdown Voltage |
4 KV AC for two minutes. |
| Acceptable Line Frequency |
48 to 65Hz. |
| Line Leakage Current |
4µA maximum. |
| Surge & Spike Suppression |
Built-in Transient absorbers of appropriate rating limits surges
& spikes of 100V/µs. |
| Impulse Energy Absorption |
Absorbs upto 30 Joules across the line. |
| Input Termination |
3 Core input cable 6 ft. long - Fuse protected. |
| Output Termination |
** NEMA / DIN / BRITISH Other Sockets as per special request. |
Size (H x W x D) (mm)
(approx.) |
152 x 165 x 292
6 x 6.5 x 11.5 |
178 x 203 x 305
7 x 8 x 12 |
229 x 254 x 330
9 x 10 x 13 |
229 x 254 x 432
9 x 10 17 |
| Weight Kg. / lbs |
9/20 |
17/38 |
31/68 |
60/132 |
| * Add suffix A to Model number for 115V, 60Hz line. |