| Technical Specifications |
| Output Voltage Regulation |
±3.0% of nominal voltage over permitted range of input voltage and load variation from no load to full load. |
| Low Power Factor |
0.8 lag to unity P.F. capacity (VA) to be derated to 75% at 0.8PF lagging load. |
| No Load Input Current |
<5% of F.L. |
| Overload Capacity |
150% of continuous rating for 10 seconds. |
| Frequency Synchronisation |
Provision of accept external sync-signal. |
| Frequency Stability |
Standard Units : ±1% of selected frequency.
Optional : ±0.005% of selected frequency with crystal control. |
| Overload & Short Circuit Protection |
Electronic current limit for short term overloads. Short circuit protection with fuses. |
| Reverse Polarity Protection |
Provided. |
| Operating Temp. Range |
-20ºC to +50ºC. |
| Input Voltage Range |
-10% to +20%. |
| Output Voltage |
115V, 220V or 240V AC selected with internal taps. |
| Output Frequency |
50/60Hz ±1% internal switch selectable. |