| Technical Specifications |
| Regulation |
Better than ±2%. |
| Ripple |
<200mV p-p. |
| Recovery Time |
1ms typical. |
| Parallel Operation |
One or more units can be used in parallel for higher power capacity. |
| INPUT |
|
| Voltage |
185 - 264 V AC, 45 - 65 Hz. |
| Current |
16 Amps typical at 230V AC. |
| Power Factor |
0.75 typical capacitive. |
| Spikes |
VDE 0843/IEC801-V-3-3. |
| Burst |
VDE 0843/IEC0801-IV-3-2. |
| RFI |
VDE 0878/EN55022-A. |
| PROTECTIONS |
|
| Over Voltage & Over Temp |
Electronic turn off for output over-voltage and over-temperature, Reset through panel push switch. |
| Indications |
LED Green = Float. LED Red = Boost. LED Red = Output Abnormal. 7 Segment DPM for output voltage & current measurement. |
| Controls |
Input ON/OFF circuit breaker. Output voltage set potentiometer. Float / Boost switch. Alarm reset - push button switch. |
| GENERAL DATA |
|
| Operating Temperature |
0ºC to +60ºC. |
| Derating |
2.5% / ºC above +40ºC. |
| Storage Temperature |
-20ºC to +70ºC. |
| Humidity |
90% without condensation. |
| Cooling |
Fan cooled with air exhaust at the rear. |
| Mechanical Construction |
19 x 4 unit high x 450 mm deep. |
| Connector |
Terminal strip for input. Brass terminals for output at the rear. |
| Weight |
Approx. 15 Kg. |