| Technical Specifications |
| RATED OUTPUT |
Refer the Selection Guide. |
Output Voltage & Current Resolution |
Refer the Selection Guide. |
Output Voltage Accuracy |
<0.05% of F.S. ±20mV. |
Output Voltage Regulation |
<0.01% of F.S. +8mV. |
Output Current Accuracy |
<0.1% of F.S. ±100mA. |
Output Current Regulation |
<0.05% of F.S. ±10mA. |
Readback Accuracy |
<±0.1% of F.S. ±1 digit for voltage.
<±0.5% of F.S. ±1 digit for current. |
Output Ripple |
CV Mode Operation : <1.0mV rms.
CC Mode Operation : <100.0mA rms. |
| PROGRAMMABLE PARAMETERS |
Setting Resolution of Output Voltage |
10mV per BIT (12 BIT DAC inside). |
Setting Resolution of Output Current |
100mA per BIT (12 BIT DAC inside). |
| INPUT PARAMETERS |
Input Voltage Range |
230V AC ±10%, 50Hz, 1 phase supply. |
| MODE OF OPERATION |
Local Mode |
Through Front Panel Potentiometers. |
Remote Mode Interface |
GPIB & RS232 (optional) interface. IEEE-488.2 & SCPI compatible. |
| OUTPUT INDICATIONS |
| Indications |
7 segment Digital Panel Meters for output voltage, current & over voltage. |
| PROTECTIONS |
Over Voltage Protection |
Available. The over voltage setting is programmable through local potentiometer as well as remote (GPIB/RS232) command. |
Over Current Protection |
Available. The over current setting is programmable through remote command (GPIB/RS232) only. |
Over Temp. Protection |
Available. |
| OPERATING TEMPERATURE |
Temperature |
0 - 40ºC (Accuracy guaranteed at 25ºC ±5ºC). |
Relative Humidity |
<80% Rh-Non condensing. |
Storage Temperature |
-20ºC to +60ºC. |
Warmup Time |
15 Minutes. |
| GENERAL |
Dimensions |
483 (W) x 133 (H) x 640 (D) mm. |
Weight |
35 Kg. approx. |